Reference

Industrial Power Modules Selection Guide

Industrial power modules target variable-frequency drives, UPS systems and welding supplies, packaging power switches together with rectifier bridges, brake units and other circuitry into application-specific topologies. This raises system power density and simplifies thermal and busbar design, letting equipment makers build the main circuit directly from a standard module rather than hand-wired discrete parts.

Reading the Key Parameters

  • Vces (blocking voltage): listed parts span three classes — 650V, 1200V and 1700V — matching different grid voltage levels and applications. Leave margin above bus voltage for switching spikes.
  • IC (rated current): listed parts range from 10A to 900A, covering everything from small welding supplies to high-power VFD drives. Derate against the actual load profile and thermal conditions.
  • VCE(sat) (typical conduction drop): listed data runs roughly 1.5–3.1V. Lower values cut conduction loss — weigh this against switching loss and frequency for overall efficiency.
  • (Eon+Eoff) (switching loss, typical @Tj=125°C): listed data spans roughly 2.3–103.8mJ, a wide range tied to current class and package/topology. It's the key input for estimating total module loss and sizing the heatsink.
  • Configuration: the catalog covers rectifier-bridge-plus-brake-plus-three-phase-output, three-phase bridge, H-bridge, chopper diode and other circuit structures — match this directly to the end circuit's main topology.

Three Steps to Select

  1. Fix the circuit structure from the required topology (rectifier+brake, three-phase bridge, H-bridge, etc.), then confirm the Vces class from bus voltage;
  2. Estimate total module loss from VCE(sat) and (Eon+Eoff) against actual load current and switching frequency;
  3. Confirm Rth(J-C) and package fit against the loss estimate and heatsink thermal-resistance budget.

Common Pitfalls

  • Selecting on current class alone while ignoring whether the topology matches the end circuit, complicating external wiring;
  • Overlooking the relationship between switching loss and frequency — loss estimated from low-frequency conditions badly understates high-frequency use;
  • Focusing only on static electrical parameters for continuous-duty equipment while ignoring reliability metrics such as power-cycling life.

More parts can be filtered by topology, voltage and current in the online selector; submit a part inquiry for specific fit questions.

Related guide: IGBT Modules Selection Guide

Go to Industrial Power Modules selector →